Flame-Proof Motors

Three phase squirrel cage explosion proof motors feature the protective "d" (flame-proof) design and comply with the European standards EN5014, EN5018 as well as IEC, CENELEC, VDE and DIN standards.

The explosion proof motor classification:
— Eexd IIB + H2 T4 (IIB group of gases as well as hydrogen, T4 Temperature class) for frame sizes 80, 90 and 100;
— Eexd IIB T4 (IIB group for gases, T4 Temperature class) for frame sizes 112, 132, 160 and 180.

Mounting dimensions are in accordance with the international standard IEC 72-1. Mounting dimension and coordination of ratings meet the qualifications of the DIN 42673 part 1 standard. Motors also comply with standard IEC 34-1 and VDE 0530 (general requirement for electrical machines).

  • IEC motors have 6 terminals in terminal box
  • < 3 kW — dual voltage 230/400
  • > 3 kW — 400 volts
  • Class F insulation
  • Class B temperature rise
  • Continuous duty
  • Top-mounted terminal box
  • Voltage ± 10%, frequency ± 5%
  • DIN-332
  • IP 54 enclosure standard — IP 55 optional
  • CE for low voltage directive
  • V.P.I. insulation system on 112–220 frame

2 pole • 3,000 RPM • IP54
FramePoleskWHPRPM Load at
100%
Cosf
100%
Inertia
(kg–m2)
Weight
(kg)
80R20.7512,81067790.0008425.0
80H21.101 1/22,80068770.0011828.0
90S21.5022,85579880.0022035.0
90L22.2032,85578890.0030038.0
100L23.0012,87081840.0055048.0
112M24.005 3/82,89085860.0065062.0
132SR25.507 3/82,85084840.0096080.0
132SH27.50102,92085850.0120084.0
160MR211.0014 3/42,93087870.03200115.0
160MR215.0020 1/92,93088880.04100125.0
160L218.5024 4/52,93090880.05000138.0
180M222.0029 1/22,96091900.01000222.0


4 pole • 1,500 RPM • IP54
FramePoleskWHPRPM Load at
100%
Cosf
100%
Inertia
(kg–m2)
Weight
(kg)
80R40.553/41,41060700.0013925.0
80H40.7511,41088730.0018528.0
90S41.101 1/21,42577800.0033834.0
90L41.5021,43076770.0043838.0
100LR42.203/41,42578760.0060046.0
100LH43.0011,43580810.0090053.0
112M44.005 3/81,44083810.0110060.0
132S45.507 3/81,45085830.0250088.0
132M47.50101,45586830.03500100.0
160MR411.0014 3/41,46088840.07100142.0
160L415.0020 1/91,46090840.09500175.0
160L418.5024 4/51,47590850.18000175.0
180L422.0029 1/21,47591840.20000210.0


6 pole • 1,000 RPM • IP54
FramePoleskWHPRPM Load at
100%
Cosf
100%
Inertia
(kg–m2)
Weight
(kg)
80R60.371/292052640.0013927.0
80H60.553/491058660.0018529.0
90S60.75193071730.0050034.0
90L61.101 1/293073740.0065037.0
100L61.50296078720.0160052.0
112M62.203/496081750.0210060.0
132S63.00496083780.0320080.0
132MR64.005 3/895084800.0400083.0
132MH65.507 3/895085800.0450087.0
160M67.501097587750.01400150.0
160L611.0014 3/498088770.20000175.0
180L615.0020 1/997588800.33000232.0


8 pole • 750 RPM • IP54
FramePoleskWHPRPM Load at
100%
Cosf
100%
Inertia
(kg–m2)
Weight
(kg)
80R80.181/469551400.0013925.0
80H80.251/368053500.0018527.0
90S80.371/270060540.0043033.0
90L80.553/470065580.0050037.0
100LR80.75171570690.0125047.0
100LH81.101 1/271072720.0160052.0
112M81.50271575740.0210058.0
132S82.20370581810.0400085.0
132M83.003/470581800.0500097.0
160MR84.005 3/873084840.12000140.0
160MH85.507 3/873085840.14000152.0
160L87.501073086870.33000175.0
180L811.0014 3/472586860.33000232.0

These tables are in printable format.